SC SOURCING BRIEFHONEYWELL · Experion Series C I/O / Analog Output

CC-PAOH01

Series C HART Analog Output Module

Series C HART Analog Output Module for analog current and hart outputs to valves and final elements, supplied against the exact Honeywell part number with system and revision compatibility checked before quotation.

BRANDHoneywell
STOCK CONFIRMATIONLead time: 2–3 days
CONDITIONBrand new and original
WARRANTY12 months

Product overview

The CC-PAOH01 is a 16-channel Series C analog-output module for 4–20 mA control signals with HART communication. Typical loads include valve positioners, I/P converters and other final control elements.

Output compliance and load resistance must be checked for the complete field loop. Confirm the matching IOTA, redundancy arrangement, actuator wiring, HART requirement, safe-state strategy and Experion release.

COMMON APPLICATIONS

Installed-system context

  • 4–20 mA valve-positioner outputs
  • HART final-element communication
  • Process analog outputs

Tell us the controller, communication network and installed panel details. That context helps prevent a visually similar but incompatible replacement.

Manufacturer
Honeywell
Part number / MPN
CC-PAOH01
Product designation
Series C HART Analog Output Module
I/O type
Analog output with HART
Platform
Experion Series C I/O
Termination
Use with compatible output IOTA
Field wiring
Confirm range, load and actuator wiring
Diagnostics
Module and channel diagnostics
Output channels
16
Output range
0 mA and 2.9–21.1 mA operating range
Nominal process signal
4–20 mA with HART support
Maximum resistive load
800 Ω
Output compliance voltage
16 V
Maximum open-circuit voltage
22 V
Response time
Within 1% of commanded value in 80 ms
Compatible IOTAs
CC-TAOX01 non-redundant 6 in; CC-TAOX11 redundant 12 in
Protection / diagnostics
Open-wire monitoring, channel diagnostics and configurable safe-state behavior

Technical values are compiled from official Honeywell product documentation for this exact article number. Always check the delivered unit nameplate and revision before installation.

What to send for verification

  • • Complete Honeywell part number and clear nameplate photo
  • • compatible IOTA and revision
  • • output range, load and HART
  • • Experion release and actuator wiring
  • • Required quantity, destination and condition

What your quotation will state

  • • Exact quoted article number
  • • New, surplus or refurbished condition
  • • Available quantity and estimated lead time
  • • Warranty and proposed shipping method

Confirm IOTA, load, HART use, revision and system release.

BUYER QUESTIONS

Frequently asked questions

What is the Honeywell CC-PAOH01?

It is a Series C HART Analog Output Module used for analog current and hart outputs to valves and final elements.

What should be checked before ordering?

Confirm the complete part number, then verify compatible iota and revision, output range, load and hart, experion release and actuator wiring.

Can a visually similar Honeywell part be used instead?

Do not select by appearance alone. Firmware, signal type, IOTA, wiring, approvals and installed-system compatibility can differ even when housings look similar.

Is the quoted module supplied with its base, IOTA or accessories?

Only the exact part number stated in the quotation is included. Companion IOTAs, bases, terminal blocks, cables, detectors, amplifiers or timers are separate unless the quotation expressly lists them.

What information is needed for a quotation?

Send the complete part number, quantity, destination, required condition and a clear nameplate photo. We will confirm the quoted revision, stock status and lead time in writing.

RELATED HONEYWELL AUTOMATION PARTS

REQUEST A QUOTATION

Check price and availability

All fields are optional. Your country is identified automatically when you submit the enquiry.

Qingtian Building, North of Xusong East 5th Street, Tongzhou District, Beijing, China